Rooted in CSA B149.1 (current edition, adopted under Ontario Reg. 212/01) and the TSSA G3 Exam Blueprint. Verify every clearance against the appliance rating plate and the current code before installation.
1. Gas properties (memorize cold)
| Property | Natural gas | Propane |
|---|---|---|
| Specific gravity (air = 1) | 0.60 (lighter) | 1.52 (heavier) |
| Heating value | ~1,000 BTU/ft³ | ~2,500 BTU/ft³ |
| Flammability limits (LEL–UEL) | 4% – 15% | 2.15% – 9.6% |
| Ignition temperature | ~1,163 °F (630 °C) | ~920 °F (493 °C) |
| Air required for combustion | 10 ft³/ft³ | 25 ft³/ft³ |
| Odorant | Mercaptan | Ethyl mercaptan |
Exam trap: propane pools in low spots (basements, pits). Natural gas rises. Ventilation strategy is different for each.
2. Clearances (default values — always check the plate)
- Type B vent connector to combustibles: 6 in (150 mm) default.
- Single-wall vent connector to combustibles: 6 in (150 mm), or per manufacturer.
- Regulator vent terminal to any building air intake: 3 m (10 ft) minimum.
- Vent termination to mechanical air intake: 1.8 m (6 ft) minimum.
- Vent termination to a window or door that opens: 300 mm (1 ft) minimum, side or below opening.
- Vent termination above grade / anticipated snow line: 300 mm (1 ft) minimum, more in snow country.
- Gas meter clearance to source of ignition: 1 m (3 ft).
3. Venting categories (know all four)
| Category | Pressure | Condensing? | Typical vent material |
|---|---|---|---|
| I | Negative | No | Type B vent (natural draft) |
| II | Negative | Yes | AL29-4C stainless (rare) |
| III | Positive | No | AL29-4C, listed positive-pressure |
| IV | Positive | Yes | PVC / CPVC / polypropylene (per mfr) |
4. Combustion air (rule-of-thumb)
- All-air-from-inside: 50 ft³ per 1,000 BTU/h input of all appliances in the space.
- Two-opening method (outdoor air): one high, one low, each sized at 1 in² per 4,000 BTU/h.
- One-opening method (outdoor air): 1 in² per 3,000 BTU/h, opening within 12 in of the ceiling.
5. Pipe sizing quick reference
Pipe sizing is table lookup, not calculation. You need three inputs:
- Total connected load in BTU/h (sum all appliance input ratings).
- Developed length from meter to farthest appliance.
- Allowable pressure drop (typically 0.5" WC for < 2 psi systems).
Look up the row (length) and column (BTU/h) in the CSA B149.1 sizing table for your pipe material. Pick the smallest pipe that carries the load. If the exam gives a floor plan, size each branch — do not size the whole system as one pipe.
6. Pressure conversions
- 1 psi = 27.7 in WC
- Standard residential inlet pressure: 7 in WC (natural gas), 11 in WC (propane)
- Manifold pressure at appliance: check rating plate — typically 3.5 in WC (NG) / 10 in WC (LP).
7. Regulator relief venting
- Vent must terminate outdoors.
- 3 m (10 ft) from any building air intake, source of ignition, or window that opens.
- Screened to prevent insect / debris entry, oriented to prevent rain intrusion.
8. Ontario-specific rules (O. Reg 212/01)
- Only a TSSA-certified gas technician (G3, G2, or G1 within scope) may install, service, or alter gas piping and appliances.
- G3 scope: appliances up to 400,000 BTU/h, under direct supervision.
- G2 scope: appliances up to 400,000 BTU/h, unsupervised.
- G1 scope: no BTU/h limit, industrial and commercial.
- All work must be recorded on the appropriate TSSA installation record.
9. Exam-day tactics
- Answer easy questions first. Flag calculations and code-lookup for a second pass.
- On pipe sizing: draw the floor plan on scrap paper before you touch the table.
- If two answers look right, the more specific one usually wins.
- "All of the above" is right more often than random. "None of the above" is a trap.
- Read every question twice. TSSA loves the words except and not.